DS8000 Service Documentation Version 7.5

Installing and testing the expansion rack storage enclosures, business class

You are here to install one or more pairs of storage enclosures in the expansion rack.

Procedure

  1. Begin the installation of the expansion rack storage enclosures at the HMC.
    1. From the navigation area, click Storage Facility Management > storage facility.
    2. From the bottom Task area, click MES Install/Remove > Install Storage Enclosure or Drives. For earlier versions, the menu item is Install Storage Enclosure or DDMs.
    3. The Install window opens and asks if you were sent from the installation or MES instructions. Click Yes.
    4. The Single Choice Message Box window opens and prompts "Select the component or enclosure you would like to install." Select Install Storage Enclosures and then click Submit.
    5. Another Single Choice Message Box window opens and prompts "Select the component you would like to install." Select Install FC-AL Storage Enclosures and then click Submit.
    6. Another Single Choice Message Box window opens and prompts "Select the Storage Facility Image you want to assign the storage enclosures to." Select the storage facility image that is shown and then click Submit.
    7. The cabling configuration window opens. Confirm that the window indicates business class cabling, then click Yes.
      Note: If the window indicates standard cabling, confirm you are using the correct section of these instructions, or contact your next level of support.
  2. Storage enclosures on multiple DA pairs can be installed at the same time. Complete the following steps:
    1. If the informational DaPairsPanel displays, click OK.
    2. The Select Device Adapter Pair window displays a list of DA pairs available for more storage enclosures on the selected storage facility image.
    3. At the rear of the expansion rack, find all the storage enclosures that you have not yet cabled and installed.
    4. Use the following figures to determine the storage enclosure location codes (ex: R3-G11).
      Figure 1. Rack 1-4 storage enclosure and I/O location codes (Models 961, 96E; business class) (rear view)
      Rack 1-4 storage enclosure and I/O location codes (Rear view of Models 961, 96E; business class)
    5. Determine the storage enclosure DA Pair ID connections for Rack-2, Rack-3, and Rack-4. Refer to the following tables.
      Table 1. Rack-2 storage enclosure pairs and DA pair IDs (business class)
      Rack-2 storage enclosure pairs containing drives Connect to Rack-1 DA Pair ID:
      R2-G01 R2-G02 3 (in Rack-1)
      R2-G03 R2-G04
      R2-G05 R2-G06
      R2-G07 R2-G08
       
      R2-G09 R2-G10 0 (in Rack-1)
      R2-G11 R2-G12
      R2-G13 R2-G14
      Table 2. Rack-3 storage enclosure pairs and DA pair IDs (business class)
      Rack-3 storage enclosure pairs containing drives Connect to Rack-1 or Rack-2 DA Pair ID:
      R3-G01 R3-G02 4 (in Rack-2)
      R3-G03 R3-G04
       
      R3-G05 R3-G06 6 (in Rack-2)
      R3-G07 R3-G08
      R3-G09 R3-G10
      R3-G11 R3-G12
       
      R3-G13 R3-G14 1 (in Rack-1)
      R3-G15 R3-G16
      R3-G17 R3-G18
      R3-G19 R3-G20
      Table 3. Rack-4 storage enclosure pairs and DA pair IDs (business class)
      Rack-4 storage enclosure pairs containing drives Connect to Rack-2 DA Pair ID:
      R4-G01 R4-G02 5 (in Rack-2)
      R4-G03 R4-G04
      R4-G05 R4-G06
      R4-G07 R4-G08
       
      R4-G09 R4-G10 7 (in Rack-2)
      R4-G11 R4-G12
      R4-G13 R4-G14
      R4-G15 R4-G16
       
      R4-G17 R4-G18 4 (in Rack-2)
      R4-G19 R4-G20
    6. At the HMC screen, select all the DA Pair IDs that will have storage enclosures installed and click OK.
    7. The Select Storage Enclosure Pairs window displays the status of the storage enclosure positions available for installation for each DA pair ID.
    8. Multi-select each storage enclosure position that you will install. Each of those positions should display the enclosure status Available for Install. Then, click OK.
      Note: If a position to be installed does not display Available for Install, it might already be installed. If it is not already installed, stop and contact next level of support.
    9. An Action Panel window displays the physical location codes of the storage enclosures to be connected. If the location codes are correct, click OK.
    10. Wait for the TextandNextButtonBean window to display.
    11. The HMC displays the expansion rack storage enclosure physical location codes to be installed for each DA pair ID.
    12. DO NOT click Next until directed in a later step.
    13. Using the HMC-displayed physical location code, see Figure 1 to determine the location of each storage enclosure being installed in the rack.
    14. Go to the next step.
  3. For each storage enclosure physical location code displayed by the HMC, ensure the four FC-AL cables are still connected to the T1 & T2 connectors (labeled J1 & J2 on the sheet metal) on both FCICs in the storage enclosure being installed. See Figure 2.
    Attention: Ensure each FC-AL cable is connected to the correct enclosure and port. Incorrect connections during this installation could result in a loss of access when additional storage is added to the affected DA pair.
    Note: These cable ends should not have been disconnected as part of this installation procedure.
    Figure 2. Storage enclosure connectors location codes
    Storage enclosure locations rear
  4. For each storage enclosure physical location code displayed by the HMC, find that location code in the first column of Table 4, Table 5, Table 6, or Table 7. Then use the information in the remaining columns to connect the FC-AL cable to the FCIC card (see Figure 2) or I/O enclosure device adapter card (see Figure 3) as appropriate.
    Attention: Ensure each FC-AL cable is connected to the correct adapter and port or enclosure and port. Incorrect connections during this installation could result in a loss of access when additional storage is added to the affected DA pair.
    Figure 3. I/O enclosure locations and device adapter card slot locations
    I/O enclosure locations and device adapter card slot locations
    Table 4. FC-AL cable connections for expansion rack storage enclosures to I/O enclosure device adapter cards
    Storage enclosure location code displayed on HMC: Physical location to connect the four FC-AL cables to:
    Rack 1 DA I/O enclosure and slot Rack 2 DA I/O enclosure and slot Connector
    R2-G07

    R1-XI3 Slot C6
    R1-XI4 Slot C3

     

    T1 & T2 (Top two connectors)
    T1 & T2 (Top two connectors)

    R2-G08

    R1-XI3 Slot C6
    R1-XI4 Slot C3

     

    T3 & T4 (Bottom two connectors)
    T3 & T4 (Bottom two connectors)

    R3-G03  

    R2-XI1 Slot C3
    R2-XI2 Slot C6

    T1 & T2 (Top two connectors)
    T1 & T2 (Top two connectors)

    R3-G04  

    R2-XI1 Slot C3
    R2-XI2 Slot C6

    T3 & T4 (Bottom two connectors)
    T3 & T4 (Bottom two connectors)

    R3-G11  

    R2-XI3 Slot C3
    R2-XI4 Slot C6

    T1 & T2 (Top two connectors)
    T1 & T2 (Top two connectors)

    R3-G12  

    R2-XI3 Slot C3
    R2-XI4 Slot C6

    T3 & T4 (Bottom two connectors)
    T3 & T4 (Bottom two connectors)

    R3-G19

    R1-XI1 Slot C6
    R1-XI2 Slot C3

     

    T1 & T2 (Top two connectors)
    T1 & T2 (Top two connectors)

    R3-G20

    R1-XI1 Slot C6
    R1-XI2 Slot C3

     

    T3 & T4 (Bottom two connectors)
    T3 & T4 (Bottom two connectors)

    R4-G07  

    R2-XI1 Slot C6
    R2-XI2 Slot C3

    T1 & T2 (Top two connectors)
    T1 & T2 (Top two connectors)

    R4-G08  

    R2-XI1 Slot C6
    R2-XI2 Slot C3

    T3 & T4 (Bottom two connectors)
    T3 & T4 (Bottom two connectors)

    R4-G15  

    R2-XI3 Slot C6
    R2-XI4 Slot C3

    T1 & T2 (Top two connectors)
    T1 & T2 (Top two connectors)

    R4-G16  

    R2-XI3 Slot C6
    R2-XI4 Slot C3

    T3 & T4 (Top two connectors)
    T3 & T4 (Top two connectors)

    Table 5. FC-AL cable connections Rack-2 storage enclosures to adjacent storage enclosures
    Expansion rack storage enclosure location code displayed on HMC: Physical location to connect the four FC-AL cables to:
    Storage enclosure Connector
    R2-G01 R2-G03 T3 & T4 on both FCIC cards
    R2-G02 R2-G04
    R2-G03 R2-G05
    R2-G04 R2-G06
    R2-G05 R2-G07
    R2-G06 R2-G08
    R2-G07 to I/O enclosure, see Table 2
    R2-G08 to I/O enclosure, see Table 2
    R2-G09 R2-G11
    R2-G10 R2-G12
    R2-G11 R2-G13
    R2-G12 R2-G14
    R2-G13 R1-G01
    R2-G14 R1-G02
    Table 6. FC-AL cable connections Rack-3 storage enclosures to adjacent storage enclosures
    Expansion rack storage enclosure location code displayed on HMC: Physical location to connect the four FC-AL cables to:
    Storage enclosure Connector
    R3-G01 R3-G03 T3 & T4 on both FCIC cards
    R3-G02 R3-G04
    R3-G03 to I/O enclosure, see Table 2
    R3-G04 to I/O enclosure, see Table 2
    R3-G05 R3-G07
    R3-G06 R3-G08
    R3-G07 R3-G09
    R3-G08 R3-G10
    R3-G09 R3-G11
    R3-G10 R3-G12
    R3-G11 to I/O enclosure, see Table 2
    R3-G12 to I/O enclosure, see Table 2
    R3-G13 R3-G15
    R3-G14 R3-G16
    R3-G15 R3-G17
    R3-G16 R3-G18
    R3-G17 R3-G19
    R3-G18 R3-G20
    R3-G19 to I/O enclosure, see Table 2
    R3-G20 to I/O enclosure, see Table 2
    Table 7. FC-AL cable connections Rack-4 storage enclosures to adjacent storage enclosures
    Expansion rack storage enclosure location code displayed on HMC: Physical location to connect the four FC-AL cables to:
    Storage enclosure Connector
    R4-G01 R4-G03 T3 & T4 on both FCIC cards
    R4-G02 R4-G04
    R4-G03 R4-G05
    R4-G04 R4-G06
    R4-G05 R4-G07
    R4-G06 R4-G08
    R4-G07 to I/O enclosure, see Table 2
    R4-G08 to I/O enclosure, see Table 2
    R4-G09 R4-G11
    R4-G10 R4-G12
    R4-G11 R4-G13
    R4-G12 R4-G14
    R4-G13 R4-G15
    R4-G14 R4-G16
    R4-G15 to I/O enclosure, see Table 2
    R4-G16 to I/O enclosure, see Table 2
    R4-G17 R4-G19
    R4-G18 R4-G20
    R4-G19 R3-G01
    R4-G20 R3-G02
  5. You have already selected all the storage enclosures to be installed at one time. Return to the HMC and click Next.
  6. The HMC automatically initializes the storage facility image the storage enclosures are being installed to.
    Note: The times that are listed are for a fully populated rack.
    The HMC displays some or all of the following messages:

    Task in Progress...Powering on the FRU(s)
    Task in Progress... Verifying the FRU power-on
    Verification Progress...Verification progress:
    Working
    Task in Progress...Activating the system (maximum of 40 minutes)
    Working...
    Task in Progress...Verifying system
    Verification Progress...Verification progress: (maximum of 35 minutes)
    Working
    Task in Progress...Activating applications (maximum of 45 minutes)
    Verification progress... Verifying applications
    Verification progress... Verification progress:
    Working

  7. A window might open indicating that the drives that are involved in this service action are now being formatted in the background. Click Next.
    Note: The actual drive state might be formatting, initializing, or certifying depending on the drive type and size. Monitor completion of the certify process later in this procedure, in the section "Finish installation and cleanup."
  8. A completion window opens that indicates:
    Installation has completed successfully
    Return to the MES or installation instructions. 

    Click Next.

When the HMC is finished, it displays:

Service action is ending...

The window closes. Go to the next step.

  1. Have all the FC-AL storage enclosures been installed in the expansion rack you are installing?
    • Yes, to go the next step.
    • No, return to step 1 to install the remaining storage enclosures.
  2. Display and repair any related open serviceable events.
  3. View the storage facility state, refer to MAP1100 View storage facility state (end of call).
    1. From the navigation area, click Storage Facility Management > storage facility.
    2. From the bottom Task area, click Service Utilities > View Storage Facility State. A window displays the status (passed/failed) of 25 or more system checks. Figure 4 is an example.
    3. All status fields should display as PASSED except for the following.
      • If the Resources State result is "Failed", select it and then click Details. If the Drive state is "5 (Certifying)", this is normal and you should go to the next step.
      • If other checks are failed, select it and then click Details. They should be fixed before going to the next step. If needed, call the next level of support.
      Note: If the Large File Transfer (the tenth System Check Type status from the top) displays as FAILED, the remaining System Check Types below it cannot be displayed. Contact the next level of support.
      Figure 4. Window: View Storage Facility State
      Window: View Storage Facility State
  4. Are you installing Rack-2 at this time?
    • Yes, go to step 13.
    • No, go to step 14
  5. Does Rack-2 contain one or more high-performance flash enclosures in locations B04, B03, B02 or B01?
  6. Will you be installing another expansion rack on this storage facility as part of this installation activity?
  7. Are you installing a Rack-2 on this storage facility as part of this installation activity?