| On |
Off |
Blank |
Normal condition, continue with the next step. |
| On |
Off |
Two-character status code other than Blank. |
Go to MAP21A1 DC-UPS fault isolation during installation. |
| Off |
Off |
- Blank (if both DSUs in the rack have loss of input power or both
have input phase setting misplugged)
- I1 (on affected DSU, if only one DSU in the rack has loss of
input power)
|
- Check the DC-UPS input phase selection setting on both DC-UPSs.
Ensure that they are the same. If the setting does not match the customer
power type, the DC-UPS will not power on and will not be damaged.
Reference Checking customer power type and DC-UPS input phase selection settings.
Note: If the customer power type is three-phase high voltage (380
- 415 V), you must use Model 961, 96E five-wire mainline power cables.
If four-wire mainline power cables from Models 951, 95E, 941, 94E
or prior are used, the DC-UPS may need to be replaced.
- If the input phase selection is correct, treat this as an customer
input power fault, reference MAP2051 Loss of AC Input to a single DC-UPS DC supply unit (DSU)
Note: If
both DC-UPSs are failing, then repeat the customer voltage checks
done previously.
|