DS8000 Service Documentation Version 7.5

Exchange the DASD fan tray assembly

Before you begin

Icon for electrostatic discharge wrist strapUse approved ESD procedures to prevent damage.

Attention:
  • This is not a stand-alone procedure. Customer disruption and damage to the hardware might occur if microcode and power boundaries are not in the proper conditions for this service action.
  • If you were sent here by a serviceable event FRU repair, the microcode and power boundaries have already been set.
  • If you were not sent here by a serviceable event FRU repair, see MAP1230 Replace a FRU without using a serviceable event.
Notes:
  • All the cables and FRUs to be removed must be uniquely identified so they can be reinstalled correctly.
  • If an installed earthquake resistance kit prevents you from accessing this FRU, refer to MAP1600.
DANGER
Hazardous voltage, current, or energy levels are present inside of a component to which this label is attached. (L001)

Safety label L001

Remove the DASD fan tray assembly

Procedure

  1. To locate this FRU, do one of the following and then return here and continue to replace the FRU:
    • If this FRU has a FRU identify indicator, use the FRU identify indicator, which is listed in MAP1240 Locating FRUs using identify indicators. If not, use the location code.
      Note: There might be cases where the FRU failure or fencing conditions prevent the FRU LED indicator from being lit even if the FRU has power.
    • Use the location code, which is listed in MAP1245 Finding FRUs by using location codes.
    • If there is no FRU identify indicator or location code, you were sent here by an isolation MAP or symbolic FRU procedure. Use the information in that procedure and the figures in this procedure to locate the proper part to exchange.
  2. Most, but not all, FRUs have identify indicators. Use the flashing amber or solid blue FRU identify indicators to ensure that you are working on the correct enclosure or FRU.
    • The "light path" identify LEDs are a hierarchy of LEDs that can identify the rack, enclosure, FRU, and even the FRU connector to which a cable is connected.
    • For more information, refer to MAP1240 Locating FRUs using identify indicators.
  3. Remove the cables from the front of the fan tray.
  4. Press down on the clasp to unlock the fan tray.
    Figure 1. Unlocking the fan tray

    Removing the fan tray

  5. Gently slide the fan tray out of its slot.
    Figure 2. Removing the fan tray

    Removing the fan tray

Install the DASD fan tray assembly

Procedure

  1. Slide the DASD fan tray assembly into its slot until the clasp snaps into place.
  2. Connect the three cables.
  3. Exit this service information center parts exchange procedure and return to the procedure that sent you here.