About this task
The UEPO switch and cable assembly is:
- The red UEPO switch is at the front of the rack above the Battery
service module (BSM) sets.
- The UEPO cable is permanently attached to the rear of the UEPO
switch.
- The UEPO switch and cable are two separate circuits. The switch
is a double pole - single throw switch. There is one set of contacts
and dedicated wires for each DC-UPS UPS.
- The DC-UPS sends
a low voltage DC signal to the UEPO switch. That signal must be returned
to the DC-UPS DSU to allow
it to power on. If the UEPO signal loop is open (UEPO switch tripped
or a cable problem), the DC-UPS DSU will not
power on at all. All LEDs will be off.
- Each rack has its own UEPO switch.