This is not a stand-alone procedure. Customer disruption and damage
to the hardware might occur if microcode and power boundaries are
not in the proper conditions for this service action.
If you were sent here by a serviceable event FRU repair, the microcode
and power boundaries have already been set.
All the cables and FRUs to be removed must be uniquely
identified so they can be reinstalled correctly.
If an installed earthquake resistance
kit prevents
you from accessing this FRU, refer to MAP1600.
Remove the rack identity card to DC-UPS cable
About this task
Note: The rack identity card to DC-UPS cable is only used
in an expansion rack (Rack-2, 3, 4). In Rack-1, the rack
identity card is cabled to the RPC cards in Rack-1.
Procedure
To locate this FRU, do one of the following
and then return here and continue to replace the FRU:
If there is no FRU identify indicator or location code, you
were sent here by an isolation MAP or symbolic FRU procedure. Use the information in that procedure
and the figures in this procedure to locate the proper part to exchange.
Most, but not all, FRUs have identify indicators. Use the flashing amber or solid blue FRU identify indicators to ensure that you are working
on the correct enclosure or FRU.
The "light path" identify LEDs are a hierarchy of LEDs that can
identify the rack, enclosure, FRU, and even the FRU connector to which a cable is
connected.