DS8000 Service Documentation Version 7.5
MAP2061 Only one DC-UPS in the
rack reports a UEPO power-off request (Model 961, 96E)
Use this procedure when only one DC-UPS of a pair
of DC-UPSs
in the same rack is reporting that the UEPO circuit loop through the
UEPO switch is open. The other DC-UPS is reporting
the UEPO circuit loop through the UEPO switch is closed (normal operation).
MAP2061 Section-1
Procedure
- Use the FRU list to determine the location of the DC-UPS reporting
the UEPO circuit open loop.
Note: All The DC-UPS LED indicators
will be off. The internal processor logic is still active.
- Is the Ex-J5 cable properly connected to rear of the DC-UPS? See Figure 1.
- Yes, continue at the next step.
- No, go to step 4.
Figure 1. Location codes for
the DC-UPS (Models 961, 96E) (rear)
- At the front of the rack, visually inspect the rack UEPO
switch. See Figure 2.
Is the switch in the full up position (not UEPO)?
- Yes, continue at the next step.
- No, the switch needs to be set to the full up position. Schedule
a time with the customer when they can stop all host activity or when
the storage facility can be powered off.
- Check the continuity of the UEPO
circuit through the UEPO cable and switch.
Note: The cable
is hard-wired to the UEPO switch. The UEPO switch and cable FRU control
both DC-UPSs
in the rack. The switch is a double-pole, single-throw switch. Each DC-UPS has its
own dedicated two-wire loop through the UEPO switch.
- Disconnect the UEPO cable from the failing DC-UPS J5 connector.
- Use a digital volt/ohm meter to check the continuity
between the two wires of the cable connector.
Is the continuity 1 ohm or less?
- Yes, the UEPO cable and switch are working properly. Return
to the screen that sent you here to replace the DC-UPS DC supply
unit (DSU)
FRU.
- No, replace the UEPO switch and attached cable. Go to Exchange the UEPO switch and cable assembly.