DS8000 Service Documentation Version 7.5
Routing and connecting the rack power control cables to the
RPC cards
Procedure
- You will perform the following steps for one expansion
rack. If you have additional expansion racks to install, you will
be sent back here later.
- To access the rear of the PPS,
unfasten
and then rotate the upper and lower
sets of power distribution units (PDUs) away from the rear of the
PPS, as shown in Figure 1. Figure 1. Power distribution units in normal position (rack rear view)
- Remove the tailgate frame bracket. Remove two screws 2 as
shown in Figure 2.
Loosen but do not remove the two top screws 1 .
Slide the bracket out.
Figure 2. Tailgate frame
bracket
- At the rear of the expansion rack being installed, find
the power control cable that connects to the PPS sequencer module
connector J1 in the upper PPS. The loose
end of the cable has a gray label.
Figure 3. PPS J1 connector
- Route the J1 cable from the
prior step to the rear upper right of Rack-1 (the location of the
RPC cards). The cable route is through the frame
to frame access holes near the rear cover upper hinges.
- Use Table 1 and Figure 4 to determine which
RPC1 card connector to plug the expansion rack power control cable
to. Connect the cable to the RPC card.
Table 1. Rack number and RPC1 connector locations| Rack number |
RPC 1 card (right card) |
| 2 |
J203 |
| 3 |
J205 |
| 4 |
J207 |
Figure 4. RPC1 cards,
connector locations (rear of rack)
- At the rear of the expansion rack being installed, find
the power control cable that connects to the PPS sequencer module
connector J2 in the upper PPS. The loose
end of the cable has a yellow label.
Figure 5. PPS J2 connector
- Route the J2 cable from the
prior step to the rear upper right of Rack-1 (the location of the
RPC cards). The cable route is through the frame
to frame access holes near the rear cover upper hinges.
- Use Table 2 and Figure 6 to determine
which RPC2 card connector to plug the expansion rack power control
cable to. Connect the cable to the RPC card.
Table 2. Rack number and RPC2 connector locations| Rack number |
RPC 2 card (left card) |
| 2 |
J203 |
| 3 |
J205 |
| 4 |
J207 |
Figure 6. RPC2 cards,
connector locations (rear of rack)
- Are you here to install the cables for Rack-2?
- All FC-AL
cables in Rack-2 are already connected, none of them go to Rack-1.
The Rack-2 SPCN and PCIe cables will be connected to Rack-1. Go to Routing and connecting the Rack-2 SPCN and PCIe cables.