DS8000 Service Documentation Version 7.5
Checking customer voltage with customer CB off (wired)
Procedure
- Prepare the multimeter to measure 1.0 V ac or less.
- Measure the voltage between each pair of voltage pins on
the female connector on each mainline power cable. Also, measure the
voltage between each voltage pin (for three phase A , B ,
and C or
for single phase A and B ) and
the ground pin on each mainline power cable. Refer to Figure 1 or Figure 2.
Did any voltage measure more than 1.0 V ac?
- Yes, inform the customer that one or more voltage pins on
the customer supply measured greater than 1.0 V ac even though the
circuit breaker is off. Do not continue until the voltage is less
than 1.0 V ac.
- No, continue with Checking customer voltage with customer CB on (wired).
Figure 1. Three-phase delta mainline
power connector at DC-UPS end
Figure 2. Single phase
mainline power connector