Use Table 1 to find the condition that applies:
| AC INPUT GOOD | UEPO LOOP GOOD | PPS Status Display | Action |
|---|---|---|---|
| On | Off | Ignore | Normal condition, continue with the next step |
| On | On | Ignore | UEPO fault, go to MAP21F0 UEPO loop good LED should be off |
| Off | Off | Ignore | Input power fault, go to MAP2050 Loss of AC Input to a single primary power supply. Note: If
both PPSs are failing, then repeat the customer voltage checks done
previously.
|
Use Table 2 to find the condition that applies.
| AC INPUT GOOD | UEPO LOOP GOOD | PPS Status Display | Action |
|---|---|---|---|
| On | On | Blank, U0, XC, or XD or a momentary
display of XA. Note: Some levels of PPS firmware will cause an
XC or XD error code to be displayed. This is a false error. The condition
will remain until the DDM power supply is turned on in a later step.
No action is required. Continue with the next step.
|
Normal condition, continue with the next step. |
| On | On | Two-character status code other than Blank, U0, XC, XE or XF. | Go to MAP21A0 PPS fault isolation during install. |
| On | Off | Ignore the status code on the display. | UEPO fault, go to MAP21E0 UEPO Loop Good LED should be on. |