Wait a maximum of 1 hour 45
minutes (1:45) for a series of status screens to be displayed.
Does the HMC display the following message?
The
installation is now complete. Return to the MES or installation instructions. - Yes. The verify process has successfully completed. Click
Next and go to the next step.
- No. If the verify process does not complete successfully and
an exception screen is displayed, call the next level of support.
Note: The installation process will normally complete and display
this message within 25 minutes. However, if the expansion rack DC-UPS
DC supply unit firmware level is lower than that of the existing rack(s),
the installation process will automatically update the expansion rack
DC-UPS firmware. This process will add up to one
hour and 20 minutes (1:20) to the installation. During a DC-UPS
firmware update, abnormal DC-UPS LED status codes are expected. Do
not reboot the HMC or recycle DC-UPS power during this update. Allow
the update to complete, and wait for the installation complete message.