Before you begin
DANGER
An
electrical outlet that is not correctly wired could place hazardous
voltage on the metal parts of the system or the devices that attach
to the system. It is the responsibility of the customer to ensure
that the outlet is correctly wired and grounded to prevent an electrical
shock. (D004)
Procedure
- Switch the customer circuit breaker to Off for the mainline
power cables.
- Attention: Use lockout and tagout procedures as defined in
the Electrical Safety for IBM® Customer
Engineers.
- Verify the CB1
main line switch on
the rear of each DC-UPS is set to Off (down).
- Connect each storage facility mainline
power cable connector to the DC-UPS.
- If the rack has a top exit
line cord feature, pull the mainline power cables up to remove excess
slack, and tighten the adjustable clamp bracket
into the clamp housing
to secure the mainline power cables.
Do not excessively tighten the clamp bracket. See Figure 1. Figure 1. Top exit line
cord clamp
- Go to the next section.