DS8000 Service Documentation Version 7.5

Checking customer voltage with customer CB off (wired)

Procedure

  1. Prepare the multimeter to measure 1.0 V ac or less.
  2. Measure the voltage between each pair of voltage pins on the female connector on each mainline power cable. Also, measure the voltage between each voltage pin (for three phase  A ,  B , and  C  or for single phase  A  and  B ) and the ground pin on each mainline power cable. Refer to Figure 1 or Figure 2. For the top exit line cord feature, refer to Figure 3 and Figure 4.

    Did any voltage measure more than 1.0 V ac?

    • Yes, inform the customer that one or more voltage pins on the customer supply measured greater than 1.0 V ac even though the circuit breaker is off. Do not continue until the voltage is less than 1.0 V ac.
    • No, continue with Checking customer voltage with customer CB on (wired).
    Figure 1. Three-phase delta mainline power connector at DC-UPS end
    Three-phase mainline power connector
    Figure 2. Single phase mainline power connector
    Single phase, mainline power connector
    Figure 3. Three phase mainline power connector (top exit line cord feature)
    Three phase mainline power connector (top exit line cord feature)
    Figure 4. Single phase mainline power connector (top exit line cord feature)
    Single phase mainline power connector (top exit line cord feature)