- Prepare the multimeter to measure 1.0 V ac or less.
- Measure the voltage at the customer's ac power
outlet between the ground pin and the building ground. See Figure 1 or Figure 2 or Figure 3 for the
ground pin (G).
Note: The customer circuit breaker that
supplies ac voltage to the customer ac power outlet should still be
off.
Is the voltage less than 1.0 V ac?
- Yes, go to step 4.
- No, continue with the following step.
Figure 1. Single-phase, 200 - 240
V, 60A, IEC60309 customer outlet pins
Figure 2. Three-phase low voltage (200 - 240 V) phase-to-phase,
60A, IEC60309 customer outlet pins
Figure 3. Three-phase high voltage (380 - 415 V) phase-to-phase,
30A, IEC60309 customer outlet pins
- Voltage is present at a customer outlet with the customer
circuit breakers off.
DANGER
Inform the customer that, even though the
circuit breaker is off, voltage higher than 1.0 V ac is measured at
the failing customer voltage outlet pins. Do not continue until the
voltage is less than 1.0 V ac. (1003)
- Prepare the multimeter to measure 1.0 ohm or
less of resistance.
- Measure the resistance between the customer AC power outlet
ground pin and the building ground. See Figure 1 or Figure 2 or Figure 3.
Is
the resistance 1.0 ohm or less?