MAP4760 Recovering from corrupted files or functions

A cluster file (dataset) or function is corrupted. If this has affected customer operations, a separate serviceable event should have been created. In many cases, customer operations will not be affected. Only Processes and/or files used by the RAS (maintenance package) processes might be affected.

About this task

There are three recommended actions:

MAP4760 Section-1

Procedure

  1. Does the serviceable event SRC = BE1E2120?
    • Yes, contact your next level of support. There is a mismatch of the code levels on the CEC enclosures clusters during the LIC update.
    • No, continue with the next step.
  2. Read the description section above.
  3. Reload the CEC enclosure code by quiescing, powering off, powering on and then resuming the CEC enclosure. Use the exchange parts option to do a pseudo repair of the System Processor Card FRU in the CEC enclosure. Pseudo repair means you use the FRU replace guided process, but when directed to actually replace the FRU, you do not actually replace it.
    1. From the navigation area, click Storage Facility Management > storage facility.
    2. From the bottom Task area, click Exchange Parts. Select the exchange option that contains the FRU to be exchanged. A window opens and displays the enclosures.
    3. Follow the guided procedures, but do not physically remove the FRU.
    4. Complete the pseudo FRU replace.
  4. Display open serviceable events to determine if the CEC code is still failing. Either the original serviceable event will have updated timestamps in the details view, or a new serviceable event will have been created. Does the CEC code appear to still be failing?