DS8000 Service Documentation Version 7.5

MAP4060 Restoring VPD after replacing the CEC enclosure VPD card

If you replace the CEC enclosure VPD card in the CEC enclosure, you must manually restore the vital product data (VPD) settings. Use this MAP to restore the settings.

About this task

MAP4060 Section-1

Procedure

  1. Ensure you are already logged into the HMC and the CEC enclosure is powered off. The power input cable to both CEC enclosure power supplies remains connected so the service processor has power.
  2. Login to the service processor ASM interface from the HMC as user celogin and password FipSce.
  3. You must manually restore/verify the VPD card settings using the following steps. This will ensure there are no undetected functional problems after the repair action is complete. Invalid or incorrect VPD settings can prevent the CEC enclosure from powering up or can cause functional problems. Not all invalid or incorrect VPD settings can be detected by the repair verify process.
  4. From the ASMI navigation, select System Configuration > Program Vital Product Data. Then select the menu option listed in the first column of Table 1.
    • The second column gives an example of a setting; this will not be your specific setting.
    • The third column directs you where to get your setting.
    Table 1. Program Vital Product Data menu option
    Menu option Example settings Source of setting information
    System Brand D0 Set to "D0" for SSD
  5. From the ASMI navigation, select System Configuration > Program Vital Product Data > System Keywords. Then select the menu option listed in the first column of Table 2.
    Table 2. System Keywords menu options
    Menu option Example settings Source of setting information
    Storage facility system type-model 9117-MMA The label on the front of the CEC enclosure, on the operator panel.
    Storage facility system serial number 10002FA The label on the front of the CEC enclosure, on the operator panel.
    Storage facility machine type-model 2107-941
    • Four-digit machine type: always use "2107".
    • Three-digit model appears on the MTMS label, located either beneath or to the left of the UEPO red switch on the rack operator panel, or above the front or rear door latch.
    Storage facility serial number 1300310 The MTMS label, located either beneath or to the left of the UEPO red switch on the rack operator panel, or above the front or rear door latch.
    System ID 01 Set to "00" for SF System 0 (This will be the upper CEC.)

    Set to "01" for SF System 1 (This will be the lower CEC.)

    Storage facility system unique ID 0004AC08196E Set to the default value that indicates the VPD card has been replaced: 0004AC0AFFF8
    Storage facility manufacturing ID 3302004 Set to current day number and year, for example: dddyyyy.
    Node ID 5005076303FFF81C The node ID is on the WWID label. The WWID label is inside the front of Rack-1, to the left of the middle cooling fan of the upper primary power supply (PPS-1). (The label is vertical.)
    Reserved Blank Leave blank.
    RB Keyword0 0 Leave as is, this is ignored.
    RB Keyword0 2 Leave as is, this is ignored.
  6. Click Save Settings and then click Continue.
  7. From the ASMI navigation, select System Configuration > Program Vital Product Data > System Enclosures. Then select the menu option listed in the first column of Table 3.
    Table 3. System Configuration menu options
    Menu option Example settings Source of setting information
    Enclosure location U789D.001.DQD53K3
    • Feature Code/Sequence Number = U789D-001
    • Enclosure serial number =DQD53K3
    The vertical label on the front of the CEC enclosure, at the far right in between the rack mounting screws.
    Feature Code/Sequence Number 789D-001 The vertical label on the front of the CEC enclosure, at the far right in between the rack mounting screws.
    Enclosure serial number DQD53K3
    Note: The label shows 9 characters total. Use the last 7 characters.
    The vertical label on the front of the CEC enclosure, at the far right in between the rack mounting screws.
    Reserved Leave blank  
  8. Click Save Settings. The Service Processor might reboot at this point. Wait until the Service Processor returns to Standby state and log onto ASM again.
  9. From the ASMI navigation, select System Configuration. Then select the menu option listed in the first column of Table 4.
    Table 4. System Enclosures menu options
    Menu option Example settings Source of setting information
    System name Server-9117-MMA-SNDQD53K3 The label on the front of the CEC enclosure, on the operator panel.
  10. From the ASMI navigation, select Performance Setup. Then select the menu option listed in the first column of Table 5.
    Table 5. Performance Setup Menu options
    Menu option Example settings Source of setting information
    Logical Memory Block Size 16 Must be set to "16" for the DS8000®.
  11. Click Save Settings. The Service Processor might reboot at this point. Wait until the Service Processor returns to Standby state before continuing with the next step.
  12. Return to the HMC repair process screen that sent you here and click Next to continue.
    Note: When the CEC enclosure is powering on, you might be presented with screens that prompt you for Capacity on Demand (CoD) codes. The DS8000 does not use CoD, so just click Done to bypass these prompts.

MAP4060 Section-2

Procedure

  1. Ensure you are already logged into the HMC and the CEC enclosure is powered off. The power input cable to both CEC enclosure power supplies remains connected so the service processor has power.
  2. Login to the service processor ASM interface from the HMC as user celogin and password FipSce.
  3. You must manually restore/verify the VPD card settings using the following steps. This will ensure there are no undetected functional problems after the repair action is complete. Invalid or incorrect VPD settings can prevent the CEC enclosure from powering up or can cause functional problems. Not all invalid or incorrect VPD settings can be detected by the repair verify process.
  4. From the ASMI navigation, select System Configuration > Program Vital Product Data. Then select the menu option listed in the first column of Table 6.
    • The second column gives an example of a setting; this will not be your specific setting.
    • The third column directs you where to get your setting.
    Table 6. Program Vital Product Data menu option
    Menu option Example settings Source of setting information
    System Brand D0 Set to "D0" for SSD
  5. From the ASMI navigation, select System Configuration > Program Vital Product Data > System Keywords. Then select the menu option listed in the first column of Table 7.
    Table 7. System Keywords menu options
    Menu option Example settings Source of setting information
    Storage facility system type-model 8205-E6C The label on the left side of the CEC front cover.
    Label also located on left side of the CEC enclosure, to the left of the fans (hidden by front cover).
    Storage facility system serial number 106D17P The label on the left side of the CEC front cover.
    Label also located on left side of the CEC enclosure, to the left of the fans (hidden by front cover).
    Storage facility machine type-model 2107-961
    • Four-digit machine type: always use "2107".
    • Three-digit model appears on the MTMS label, located above the front door latch handle or on the rack UEPO panel behind the front door.
    Storage facility serial number 75FK810 The MTMS label, located above the front door latch handle or on the rack UEPO panel behind the front door.
    System ID 01 Set to "00" for SF System 0 (This will be the upper CEC.)

    Set to "01" for SF System 1 (This will be the lower CEC.)

    Storage facility system unique ID 0004AC08196E Set to the default value that indicates the VPD card has been replaced: 0004AC0AFFF8
    Storage facility manufacturing ID 3302011 Set to current day number and year, for example: dddyyyy.
    Node ID 5005076303FFF81C The node ID is on the WWID label. The WWID label is on the inside front left wall of the rack, near the top of the upper UPS.
    Reserved Blank Leave blank.
    RB Keyword0 0 Leave as is, this is ignored.
    RB Keyword0 2 Leave as is, this is ignored.
  6. Click Save Settings and then click Continue.
  7. From the ASMI navigation, select System Configuration > Program Vital Product Data > System Enclosures. Then select the menu option listed in the first column of Table 8.
    Table 8. System Configuration menu options
    Menu option Example settings Source of setting information
    Enclosure location U78AA.001.WIH002F
    • Feature Code/Sequence Number = U78AA-001
    • Enclosure serial number = WIH002F
    The label on the right side of the CEC enclosure, to the right of the disk drive enclosure (hidden by front cover).
    Feature Code/Sequence Number 78AA-001 The label on the right side of the CEC enclosure, to the right of the disk drive enclosure (hidden by front cover).
    Enclosure serial number WIH002F
    Note: The label shows 9 characters total. Use the last 7 characters.
    The label on the right side of the CEC enclosure, to the right of the disk drive enclosure (hidden by front cover).
    Reserved Leave blank  
  8. Click Save Settings. The Service Processor might reboot at this point. Wait until the Service Processor returns to Standby state and log onto ASM again.
  9. From the ASMI navigation, select System Configuration. Then select the menu option listed in the first column of Table 9.
    Table 9. System Enclosures menu options
    Menu option Example settings Source of setting information
    System name Server-8205-E6C-SN106D17P The label on the left side of the CEC front cover. Label also located on left side of the CEC enclosure, to the left of the fans (hidden by front cover).
  10. From the ASMI navigation, select Performance Setup. Then select the menu option listed in the first column of Table 10.
    Table 10. Performance Setup Menu options
    Menu option Example settings Source of setting information
    Logical Memory Block Size 16 Must be set to "16" for the DS8000.
  11. Click Save Settings. The Service Processor might reboot at this point. Wait until the Service Processor returns to Standby state before continuing with the next step.
  12. Return to the HMC repair process screen that sent you here and click Next to continue.
    Note: When the CEC enclosure is powering on, you might be presented with screens that prompt you for Capacity on Demand (CoD) codes. The DS8000 does not use CoD, so just click Done to bypass these prompts.