The I/O enclosure device adapter card is reporting a problem
with one or more FC-AL cables. The problem cable may have a visual
problem; unplugged, partially plugged or physically damaged or other
problem such as an internal failure. The device adapter card is listed
in the serviceable event FRU list. See Figure 1 and Figure 2.
Inspect
the FC-AL cables. Did you find a visible problem?
Yes, go to the next step.
No, if the failing FC-AL cables are listed in the FRU list,
go to the next step to replace that cable. If no cable is listed, contact your next
level of support.
Figure 1. Model 941/94E location codes for the device adapter card
Figure 2. Model 951/95E, 961/96E location codes for the device adapter
card
Use the normal FRU exchange process to do a pseudo repair
of the I/O enclosure device adapter card in the FRU list. Do not replace
the I/O enclosure device adapter card when instructed by the repair
process. Instead, correct the cable or cables that are not connected
correctly and then continue with normal repair process.
Read all of the following substeps before you continue
to the next substep. To view this MAP in a separate information center
window, click Help in the upper right corner
of the main HMC GUI screen and navigate to MAP32B0.
Click Close in the current service
information center window.
One or more HMC repair screens might prompt you for
the result of using the service procedure in the MAP. Select Problem
not fixed.
Select No when prompted for whether
you exchanged any parts.
Select Yes when prompted for
whether you isolated the problem.
Select the I/O Enclosure Device Adapter Card from
the FRU list. The HMC begins the FRU exchange process for the selected
FRU.
If the pseudo repair does not fix the problem, contact your next
level of support.