| If you are replacing just one BSM set, you may
have accidentally swapped one or more old and new BSM modules. It
is also possible, although not likely, that the new BSM set came from
IBM with a serial number mismatch. It must be replaced with a BSM
set that has matching serial numbers.
|
If you only need to correct one BSM module set:- Select the next FRU in the serviceable event FRU list to repair.
- When you are directed to replace all the BSM modules, disconnect
and undock all the modules as directed; but only replace the incorrect
module.
|
| If you are replacing more than one BSM set,
you may have accidentally swapped BSM modules between some combination
of the new set, or old set, or both. |
If you need to correct more than one BSM module
set on the same DC-UPS: - Do a pseudo repair of the DC-UPS DSU. Refer
to MAP1230 Replace a FRU without using a serviceable event. The upper DC-UPS
DSU is E1, the lower is E2. See Figure 1.
- When you are directed to replace the DC-UPS DSU, disconnect all
the cables as directed, except for the ground cable.
- At the front of the rack, undock each primary BSM as
directed by the DSU repair procedure. The DSU modules can be left
installed in the DC-UPS chassis.
- At the front of the rack, move the BSM modules to the
correct locations. Insert the primary BSM(s) and install the retaining
screw(s). Reinstall the BSM set cover (if removed).
- Return to the rear of the rack and complete the pseudo
repair of the DC-UPS DSU, connecting the cables when directed.
|