Both PPSs
have reported an overcurrent condition for one or more of the 5/12 VDC device
power boundaries in the affected rack. The affected storage enclosures (front
or back) will not be powered and access to customer data could be lost.
About this task
Each DDM within a storage enclosure contains a self-healing fuse.
In addition, the FCIC logic card has built in current limiting to provide
overcurrent protection. The following is a list of the components in the voltage
distribution path, all of which could introduce a short.
- Main DDM module in each PPS
- Optional DDM module in each PPS (if
installed)
- Cable between the DDM power modules and the secondary device distribution
bus bar
- Secondary device distribution bus bar mounted at the back center of the
machine
- Primary device distribution bus bar which runs vertically between the
device enclosures
- Bus bar jumpers between the primary and secondary device distribution
bus bar
- Cable between each storage enclosure backplane and the primary device
distribution bus bar
- Storage enclosure backplane
- FCIC logic cards
- DDMs