A cable can cause a failure if it is unplugged, incorrectly
plugged, or otherwise damaged. MAP2030 guides you through visually
inspecting the cable before you replace any FRUs. If an obvious cable
problem is found, this MAP guides you to bypass replacing active FRUs
and replacing only the cable.
About this task
An unplugged, incorrectly plugged, or otherwise
damaged cable can cause a failure. Some cable failures can be found
by visual inspection. If a cable is in the FRU list, it usually means
the problem was detected in the interface or through a connection
between two or three active FRUs. There are two types of interface
failures:
- All signals in the cable fail. This
normally is an unplugged cable. There is a greater chance of
finding cable failure by visual inspection.
- Some signals in the cable work correctly. This normally is internal or connector damage. There
is less chance of finding cable failure by visual inspection.
MAP2030 is normally only included at the top of the FRU
list if the failure is for all signals in the cable. In general,
the active logic or power FRUs at each end of the cable have a much
higher probability of failure than a passive interconnect cable FRU.
Therefore, the passive cable is normally listed last in the FRU list.
Repairs occur by replacing the highest to lowest probability
FRUs, one at a time. The only exception is where a visual inspection
of the cable reveals it is unplugged, incorrectly plugged, or severely
damaged. In this case, there is no reason to replace active FRUs.
Instead the first FRU to be replaced should be the cable.
Table 1 includes
a sample FRU list.
Table 1. Sample
FRU list for MAP2030 (Model 94x/95x FRUs shown,
Model 96x similar)| Part number |
Class |
FRU description |
Location code |
| MAP2030 |
Isolate procedure |
N/A |
N/A |
| PSPRPWR |
FRU |
Primary power supply |
U2421.A01.75DK360-E1 |
| RPCCARD |
N/A |
RPC card |
U2421.A01.75DK360-C1 |
| PSCBL0E |
Symbolic procedure |
RPC/PPS interface power
cable |
U2421.A01.75DK360-C1-T201 |
| CBLCONT |
Symbolic procedure |
Other end of RPC/PPS
interface power cable |
U2421.A01.75DK360-E1-T1 |
| CBLCONT |
Symbolic procedure |
Other end of RPC/PPS
interface power cable |
U2421.A01.75DK360-E2-T1 |
Notes: - The interconnect cable is a Y cable;
it connects the RPC card to both primary power supplies.
- In the part number column, PSCBL0E is the FRU to select to begin
the parts exchange process for this cable. That process puts the
proper resource, in this case, the RPC card, the cable attaches to,
in the proper state to allow the cable to be replaced and properly
verified.
- In the part number column, both CBLCONTs are listed for informational
purposes only. The location codes provided are used to visually inspect
the remaining ends of the cable. The service boundary associated
with each CBLCONT will not allow a proper repair of the cable and,
therefore, cannot be selected to be repaired.