This section contains rack power and cooling FRUs that
have LED indicators. Each listed assembly is shown with a description
of its LEDs. Although LED indicators may indicate a failure, they
should not be used as a starting point for a repair.
Rack power and cooling FRUs with LEDs
Table 1. Parts of the
rack power and cooling assembly that contain LEDs| Assembly |
Reference |
| Battery service module (BSM) set |
Figure 2 |
| DC-UPS DC supply unit (DSU) |
Figure 1 |
| Local
remote switch card |
Figure 4 |
| Power distribution unit |
Figure 3 |
| Power
junction assembly (PJA) |
Figure 8 |
| Rack identity card |
Figure 5 |
| Rack operator panel assembly |
Figure 6 |
| RPC card |
Figure 7 |
LEDs on the DC Supply Unit (DSU)
Figure 1. LEDs on the DC-UPS DC Supply Unit (DSU), rear of rack
Table 2. Interpreting LEDs
on the DC Supply Unit (DSU), rear of rack| Index |
LED Function |
Color |
LED Off |
LED On |
LED Flash |
| 1 |
DDM output |
Green |
Output off |
Normal |
Error1 |
| 2 |
Main output |
Green |
Output off |
Normal |
Error1 |
| 3 |
Input from partner DSU |
Green |
Error1 |
Normal |
N/A |
| 4 |
Digital status code display2 |
|
|
|
|
| 5 |
LOCAL AC (input) |
Green |
Input off |
Normal |
Error |
| 6 |
DSU SERVICE |
Amber |
Normal |
Error |
Identify |
| 7 |
AC MISMATCH (input) |
Amber |
Normal |
Error |
N/A |
| 8 |
Processor is operational3 |
Green |
Error |
N/A |
Normal |
Notes: - Error on local or partner DSU. Repair using serviceable event.
- See MAP2341 Codes on the DC-UPS DSU status display for
status code description. Repair using serviceable event.
- This LED is for manufacturing only, it is not used for field service.
|
LEDs on the Battery Service Module (BSM) set
Figure 2. Battery service module, primary,
locations (front)
Table 3. Interpreting
LEDs on the BSM set| Index |
LED Function |
Color |
LED Off |
LED On |
LED Flash |
| 1 |
Charger status |
Green |
On battery |
Normal |
Charging |
| 2 |
Fault/Identity |
Amber |
N/A |
Fault |
Identify |
| 3 |
On Battery |
Red |
Normal |
On battery |
N/A |
LEDs on the Power Distribution Unit
Figure 3. Output power indicator (LED) for a power distribution
unit
Table 4. Interpreting LEDs on
the power distribution unit| Index |
LED Function |
Color |
LED Off |
LED On |
LED Flash |
| 1 |
Output power |
Green |
Off1 |
Normal |
n/a |
Note 1: Each power output port
is protected by a non-replaceable fuse. If only one output power LED
is off, there is a problem with the power distribution unit.
LED on the local remote switch card
Figure 4. Local remote card cables
Table 5. Interpreting LEDs
on the local remote switch card | Index |
LED Function |
Location |
Color |
LED Off |
LED On |
LED Flash |
| 3 |
Identify |
C6 |
Amber |
Normal |
N/A |
Identify |
LEDs on the rack identity card
Figure 5. LEDs on the rack identity card
Table 6. Interpreting
LEDs on the rack identity card| Index |
LED Function |
Location |
Color |
LED Off |
LED On |
LED Flash |
| 1 |
Identify |
C5 |
Amber |
Normal |
N/A |
Identify |
LEDs on the rack operator panel assembly
Figure 6. Rack operator panel LEDs on
upper right of rack front cover
Table 7. Interpreting LEDs
on the rack operator panel
assembly| Index |
LED Function |
Color |
LED Off |
LED On |
LED Flash |
| 1 |
Line cord 1 |
Green |
1 |
2 |
3 |
| 2 |
Line cord 2 |
Green |
1 |
2 |
3 |
| 3 |
Identify or System Attention |
Amber |
Normal |
Attention4 (Rack-1
only) |
Identify4 |
Notes: - Off under any of the following conditions:
- Customer power is not present
- Standby power is present and the Remote Force Power Off is not
active
- The corresponding RPC or DC-UPS is fenced
- The LED is broken
- On solid when DC-UPS DDM power
is on.
- Flashes slow (1 flash per 2 seconds) when a DC-UPS is in
Standby, a DC-UPS is
not fenced, or the Remote Force Power Off switch is active. Flashes
rapidly (2 flashes per second) during the DC-UPS power
ON, power OFF, and Force Power OFF sequences.
- This LED is used for the following purposes:
- For Rack-1 only:
If the LED is lit solid, it indicates Attention
status, which means that one or more open serviceable events needing
repair exist.
When all serviceable events have been closed
or cancelled, the LED changes to off.
When both attention and
identify status exist on Rack 1, the identify indication is shown
and the LED flashes.
- For all racks:
If the LED is flashing, it indicates Identify
status, which means the service representative is replacing a part
that was selected from a serviceable FRU list or from the Parts
Exchange menu option.
Note: Most, but not all, FRUs have identify
indicators. The "light path" identify LEDs are a hierarchy of LEDs
that can identify the rack, enclosure, FRU, and even the FRU connector
for which a cable is connected.
|
LEDs on the RPC cards
Figure 7. LEDs on the RPC cards
Table 8. Interpreting upper LEDs on the
RPC cards| Index |
LED Function |
Color |
LED Off |
LED On |
LED Flash |
| 1 |
Operational |
Green |
Fenced, not booted, or no input power |
operational |
N/A |
| 2 |
Identify |
Amber |
Normal |
1 |
Identify |
Notes: - When this LED is on solid, the flash memory in the other RPC card is corrupted.
|
Table 9. Interpreting Lower LEDs on the RPC cards (Only
for use by next level of support.)| LED |
Status 0 (upper) |
Status 1 (lower) |
| On solid |
Normal operation |
Normal operation |
| 1 flash |
Watchdog timeout history |
Primary clock check, card is operational |
| 2 flash |
SSRAM parity check history |
Other RPC card is fencing this RPC card |
| 3 flash |
FPGA CRC check history |
Card ID parity check, card is not operational |
| 4 flash |
FPGA heartbeat check history |
RPC power fault |
| 5 flash |
Code not operational |
(not used) |
| OFF |
Not operational |
Secondary clock check or not operational |
LEDs on the power junction assembly (PJA)
Figure 8. Power junction assembly (PJA)
locations
Table 10. Interpreting LEDs on the power junction assembly
(PJA)| Index |
LED Function |
Color |
LED Off |
LED On |
LED Flash |
| J1 |
12V output |
Green |
No output power to fan |
Normal |
N/A |
| J2 |
12V output |
Green |
No output power to fan |
Normal |
N/A |
| J3 |
12V input |
Green |
No input power from power supply, 12V |
Normal |
N/A |
| J4 |
12V output |
Green |
No 12V output power to Ethernet switch |
Normal |
N/A |
| J5 |
12V input |
Green |
No input power from power supply, 12V |
Normal |
N/A |
| J6 |
12V output |
Green |
No 12V output power to Ethernet switch |
Normal |
N/A |
| J7 |
20V input |
Green |
No input power from power supply, 20V |
Normal |
N/A |
| J8 |
20V output |
Green |
No 20V output power to management console
laptop |
Normal |
N/A |