DS8000 Service Documentation Version 7.5

Installing hardware removed by weight reduction feature code 0200

Feature code 0200 removes storage enclosures and sometimes battery modules to reduce the shipping weight of a rack. This is required if the weight limit of building floors or elevators is less than the weight of a fully loaded rack. The parts that are removed are shipped on separate pallets. Feature code 0200 can be installed by:
The instructions describe how to:

Copies of the Weight Reduction Status chart are in the CE envelope which may be taped to the front covers, or may be in the document enclosure (front upper left of rack) and each box on the pallet.

Attention: The DS8000® retains configuration information that was established during manufacture. If all components are not reinstalled into their original locations, significant problems will result.
CAUTION:
The weight of a fully populated storage enclosure exceeds the safe lifting limit for one service representative. Installation of this feature requires two service representatives.

To determine the estimated weight of a rack, use Table 1.

Table 1. Rack weight (estimated) after all shipping materials have been removed



Rack model

Rack weight
without FC 0200
(non-reduced weight)1, 2

Rack weight
with FC 0200
(reduced weight)1, 2

921, 931 1243 kg (2740 lbs) 934 kg (2060 lbs)
922, 9A2, 932, 9B2 1313 kg (2895 lbs) 950 kg (2095 lbs)

92E, 9AE
   with FC 13003
   without FC 13004


1338 kg (2950 lbs)
1089 kg (2400 lbs)

  
776 kg (1710 lbs)
689 kg (1520 lbs)

Notes:
  1. If the shipping materials are still in place on the rack, add the following weight:
    • If the rack is in the carton but not crated, add 115 kg (250 lbs)
    • If the rack is in the carton and crated without desiccant/barrier bag, add 140 kg (310 lbs)
    • If the rack is in the carton and crated with desiccant/barrier bag, add 147 kg (325 lbs)
  2. The estimated weights assume that both primary power supplies (PPSs) in the rack contain booster modules. (From the rear of the rack, if a booster module is present it is at the top of the PPS in the horizontal orientation.) If booster modules are not present, subtract 11kg (25 lbs) from the rack weight.
  3. Four I/O enclosures.
  4. No I/O enclosures.

Continue with Installing battery module sets.