- Remove
the lockout tag and/or device that was applied to each customer mainline
AC voltage circuit breaker, then switch on the customer circuit breaker.
- Prepare the multimeter to read line voltage AC.
DANGER
Dangerous voltages may be present. Do not touch the
internal parts (pins and connectors) of the customer receptacle.
- Select the condition that applies:
- Customer power is single phase (200 - 240
V). Go to step 4.
- Customer power is three-phase low voltage
(200 - 240 V). Go to step 5
- Customer power is three-phase
high voltage (380 - 415 V). Go to step 7.
- Single-phase (200 - 240
V), measure the voltage between voltage pins A and B .
See Figure 1.
- The nominal customer voltage of single-phase is 200
- 240 V (phase-to-phase).
- The measured voltage must be between the minimum and
maximum voltages of 180 - 264 V.
Is the measured voltage between 180 - 264 V?
- Yes, go to 9.
- No, inform the customer that the voltages are not correct. Do
not continue until the voltages are correct.
Figure 1. Single-phase, 200 - 240
V, 60A, IEC60309 customer outlet pins
- Three-phase low voltage (200 - 240
V), at the customer outlet, measure the customer three-phase voltage
to ensure it is within the DC-UPS minimum and maximum input voltages.
- The nominal customer voltage of three-phase
low voltage is 200 - 240 V (phase-to-phase).
- The measured voltage must be between the minimum and
maximum voltages of 180-264V.
- Measure the voltages between each pair of voltage pins
( A to B , B to C ,
and C to A )
on the customer outlet. See Figure 2.
Are all three measured voltages between 180-264V?
- Yes, go to the next step.
- No, inform the customer that the voltages are not correct. Do
not continue until the voltages are correct.
Figure 2. Three-phase low voltage (200 - 240 V) phase-to-phase,
60A, IEC60309 customer outlet pins
- At the customer outlet,
measure the voltage between each voltage pin and ground ( A to
(G), B to (G), and C to
(G)). See Figure 1.
Are the voltages within 10% of each other?
- Yes, go to step 9.
- No, inform the customer that the voltages are not correct. Do
not continue until the voltages are correct.
- Three-phase high voltage (380 - 415 V) at
customer outlet, measure the customer three-phase voltage to ensure
it is within the DC-UPS minimum and maximum input voltages.
- The nominal customer voltage of three-phase
high-voltage is 380 - 415 V (phase-to-phase).
- The measured voltage must be between the minimum and
maximum voltages of 342 - 456 V.
- Measure the voltages between each pair of voltage pins
( A to B , B to C ,
and C to A )
on the customer outlet. See Figure 3.
Are all three measured voltages between 342-456V?
- Yes, go to the next step.
- No, inform the customer that the voltages are not correct. Do
not continue until the voltages are correct.
Figure 3. Three-phase high voltage (380 - 415 V) phase-to-phase,
30A, IEC60309 customer outlet pins
- At the customer outlet, measure
the voltage between each voltage pin and ground ( A
to (G), B to (G), and C
to (G)). See Figure 1.
Are the voltages within 10% of each other?
- Yes, go to the next step.
- No, inform the customer that the voltages are not correct. Do
not continue until the voltages are correct.
- Continue with Connecting the mainline power cables on the racks (plug in).