DS8000 Service Documentation Version 6.3.3
Checking customer preparations
Before you begin
DANGER
HEAVY EQUIPMENT: PERSONAL INJURY OR EQUIPMENT DAMAGE MAY
RESULT IF MISHANDLED (D006)
Procedure
- Verify that the customer has two AC power
sources for each rack in the storage facility.
For maximum fault tolerance, use two separate AC power sources.
Note: The storage facility is designed for connection to an IT power distribution system. In an IT power distribution system, the neutral conductor is isolated from earth (ground) by an impedance with exposed conductive parts in the installation that is tied directly to earth.No service representative action is needed. Information is for compliance with International Electrotechnical Commission Standard 950 for the safety of information technology equipment and electrical business equipment.
- Verify the customer wall circuit breaker.
The customer wall circuit breaker rating that protects each line cord
depends on the voltage range as follows:
- Low-voltage, three-phase installations (200 - 240 V) require wall circuit breakers that have a rating of 50 to 60 A. Do not exceed the wire rating of the facility.
- High-voltage, three-phase installations (380 - 480 V) require wall circuit breakers that have a rating of 30 to 35 A. Do not exceed the wire rating of the facility.
- If the storage facility will be installed
on a raised floor:
- Review the weight of each rack with the customer to verify that their raised floors have adequate support. An individual rack, fully configured can weigh a maximum of 2880 pounds (1307 kilograms). For details on the rack weights, refer to IBM® System Storage® DS8000 Introduction and Planning Guide.
- To correctly cool a rack, place two floor tiles, that have holes for air flow, directly in the front and the rear of each rack (for a total of 4).
- To allow cable entry, place floor tiles with appropriate cutouts under the rear tailgate.
- If the storage facility will not be installed
on a raised floor, ensure the customer will provide adequate air flow
and temperature around the storage facility. Notes:
- For information about the temperature requirements of the operating environment, see the IBM System Storage DS8000 Introduction and Planning Guide. The PDF is also available on the IBM DS8000 series Service Documents CDROM.
- The rack cooling airflow enters through the front and rear covers and exits through the top and rear covers. The bottom of the DS8000® is sealed.
- If you are installing a Rack-2
and it contains host adapter cards in the I/O enclosures at the bottom
of the rack, ensure the customer has ordered, supplied, and routed
the following cables to the storage facility being installed. Routing
of the customer cables must not be billed against the installation.
If the customer wants the service representative to route the cables,
that activity must be coded or billed separately.
- Fibre-Channel host cables from the host to the storage facility host adapters.