The part indicated in the FRU callout that follows this procedure is invalid or missing for this system's configuration.
Procedure
- Does word 8 of the reference code end with 02 or 04? Table 1 shows the reference code format.
Key:
TTTT = Reference code type
UUUU = Unit reference code
- Yes, continue with the next step.
- No, go to step 3.
- The FRU that is called out after this procedure is either missing or invalid. Is that FRU installed and connected or plugged in properly?
- Yes, remove that FRU. Then contact your next level of support to determine the correct FRU. This ends the procedure.
- No, contact your next level of support to determine the correct FRU. This ends the procedure.
- Does word 8 end with 01 or 05?
- Yes, the FRU that is called out after this procedure has the same serial number as another FRU in the system. Remove all but one of the FRUs that are called out after this procedure, and then perform a slow boot. See MAP4820 Performing a slow boot of a CEC enclosure. This ends the procedure.
- No, return to Start here. This ends the procedure.