DS8000 Service Documentation Version 6.3.3
Routing FC-AL cables, Rack-3 or Rack-4
About this task
Note: If an FC-AL cable is
damaged, you can use the point-to-point cabling diagrams to determine the other end of the cable.
See Point-to-point cabling diagrams - FC-AL cables. Several FC-AL cables are tightly bundled together so
it is difficult to physically trace an individual FC-AL cable from end to end.
Procedure
- Find and uncoil the FC-AL cables that are coiled at the rear of the expansion rack you are installing. Do not remove the black protective cable connector covers.
- Determine the destination rack and storage enclosure for
each FC-AL cable.
- Find the location code label at the free end of each FC-AL cable.
- If the labels include the physical location code (example: R2-G01-P1-C1-T2) refer to Figure 1 and Figure 2 and Figure 3 to translate to the destination storage enclosure. Then go to step 3.
- If the labels include only the three-character connection designators (example: 4A1), refer to Figure 2 and Figure 3 to translate to the destination storage enclosure. Then go to step 3.
Figure 1. Cable labels, storage and I/O enclosure locations for physical location codes
Figure 2. Point-to-point cabling diagram for the FC-AL cables (Models 951, 95E - Rack-1 Configuration: AE1) (rear view, racks 1-2)
Figure 3. Point-to-point cabling diagram for the FC-AL cables (Models 951, 95E - Rack-1 Configuration: AE1) (rear view, racks 3-4)
- Route the FC-AL cables to the destination
rack.
- Do not connect the FC-AL cables to the storage enclosure Fibre Channel interface cards until directed later in this procedure.
- Route each cable bundle to the destination rack through the rack to rack holes near the rack cover upper hinges at the rear of each rack.
- Route the FC-AL cables to the destination storage enclosure.
- Do not connect the FC-AL cables to the storage enclosure Fibre Channel interface cards until directed later in this procedure.
- FC-AL cables that will connect to the Fibre Channel interface card in the left side of a storage enclosure
are routed down the left side of the rack.
- Left-side cables have "C1" in the location code (e.g. Rx-XIx-P1-C1-Tx), or the last character in the connection designator will be odd (e.g. 2A5).
- FC-AL cables that will connect to the to the right Fibre Channel interface card in a storage enclosure are routed down
the right side of the rack.
- Right-side cables have "C2" in the location code (e.g. Rx-XIx-P1-C1-Tx), or the last character in the connection designator will be even (e.g. 2A6).
- Do not remove the black rubber protective connector covers at the end of each cable. Do not connect the cables until directed later in the install.
- Find
the expansion rack you are installing in the first column of the following
table and then use the Go to: column to continue the installation.
Expansion rack position Go to: Rack-3 Installing and testing the Rack-3 storage enclosures Rack-4 Installing and testing the Rack-4 storage enclosures.