MAP4F20 SRCs BE40020x unavailable resource recovery
This procedure recovers an unavailable CEC enclosure or I/O enclosure to operational.
MAP4F20 Section-1
About this task
Find the system reference code (SRC) in the serviceable event that sent you here in Table 1 and perform the action listed.
| SRC | Definition | Go to: |
|---|---|---|
| BE400201 | CEC found unavailable during an I/O enclosure repair. | MAP4F20 Section-2 |
| BE400202 | CEC found unavailable during a CEC RIO repair. | MAP4F20 Section-3 |
| BE400203 | I/O enclosure found unavailable during a CEC enclosure repair. | MAP4F20 Section-4 |
| BE400204 | I/O enclosure found unavailable during an I/O enclosure power/cooling repair. | MAP4F20 Section-5 |
MAP4F20 Section-2
About this task
Use this procedure after the original I/O enclosure failure has been successfully repaired. This procedure will make the CEC available and will restore the storage facility to dual CEC operational.
- You completed replacing one or more of the following I/O enclosure
FRUs:
- I/O enclosure PCIe/SPCN card
- I/O enclosure I/O backplane assembly
- I/O enclosure PCIe cable
- The serviceable event that you just repaired has been automatically closed.
- A new serviceable event was created with "SRC BE400201 = CEC found unavailable during an I/O enclosure repair." A CEC enclosure is unavailable, quiesced, or powered off.
Procedure
MAP4F20 Section-3
About this task
Use this procedure after the original CEC enclosure RIO interface failure has been successfully repaired. This procedure will make the CEC available and will restore the storage facility to dual CEC to operational.
- You completed replacing a CEC enclosure RIO card FRU.
- The serviceable event that you just repaired has been automatically closed.
- A new serviceable event was created with "SRC BE400202 = CEC found unavailable during a CEC RIO repair." A CEC enclosure is unavailable or in service mode.
Perform the following actions:
Procedure
MAP4F20 Section-4
About this task
Situation 1:
- You completed replacing a CEC enclosure FRU.
- The serviceable event for the CEC enclosure has been automatically closed.
- A new serviceable event was created with "SRC BE400203 = I/O enclosure found unavailable during a CEC enclosure repair." An I/O enclosure is unavailable, quiesced, or powered off.
Situation 2:
- A CEC enclosure FRU repair failed.
- The serviceable event for the CEC enclosure is not closed.
- A new serviceable event was created with "SRC BE400203 = I/O enclosure found unavailable during a CEC enclosure repair." An I/O enclosure is unavailable or in service mode.
Perform the following actions:
Procedure
MAP4F20 Section-5
About this task
Use this procedure after the I/O enclosure power or cooling failures have been successfully repaired. This procedure will recover the I/O enclosure to operational.
- You completed replacing one or more of the following I/O enclosure
power or cooling FRUs:
- I/O enclosure PCIe/SPCN card
- I/O enclosure backplane assembly
- I/O enclosure fan
- I/O enclosure power supply
- The serviceable events for the I/O enclosure power or cooling FRUs have been automatically closed.
- A new serviceable event was created with "SRC BE400204 = I/O enclosure found unavailable during an I/O enclosure power/cooling repair." An I/O enclosure is unavailable, quiesced, or powered off.