DS8000 Service Documentation Version 6.3.3
Checking customer receptacle ground pin continuity with customer CB off (plug in)
Procedure
- Prepare the multimeter to measure 1.0 V ac or less. Measure
the voltage at the customer's AC power outlet between the ground pin
and the building ground.
Is the voltage less than 1.0 V ac?
- Yes, go to step 3.
- No, continue with the following step.
- Voltage is present at a customer outlet with the customer
circuit breakers off. DANGERInform the customer that, even though the circuit breaker is off, voltage higher than 1.0 V ac is measured at the failing customer voltage outlet pins. Do not continue until the voltage is less than 1.0 V ac. (1003)
- Prepare the multimeter to measure 1.0 ohm or less of resistance.
- Measure the resistance between the customer AC power outlet
ground pin and the building ground. Refer to Figure 1 or Figure 2 for
the location of the ground pin.
Is the resistance 1.0 ohm or less?
- Yes, continue with the next section.
- No, inform the customer. Do not continue until the resistance is 1.0 ohm or less.
Figure 1. Three-phase amp
Figure 2. Single phase, ground pin