Checking customer ground continuity with customer CB off (wired)
Procedure
- Prepare the multimeter to measure 1.0 V ac or less. Measure the
voltage on the female ground pin on each mainline power cable and building
ground. Refer to Figure 1 or Figure 2.
Is the voltage less than 1.0 V ac?
- Yes, go to step 3.
- No, continue at the following step.
Figure 1. Three-phase mainline power connector
Figure 2. Single phase mainline power connector
- Voltage is present at a customer outlet with the customer circuit
breakers off. DANGERInform the customer that even though the circuit breaker is off, voltage higher than 1.0 V ac is measured at the failing customer voltage outlet pins.
Do not continue until the voltage is less than 1.0 V ac.
- Prepare the multimeter to measure 1.0 ohm or less of resistance.
- Measure the resistance between the female connector ground pin
on each mainline power cable and the building ground.
Is the resistance 1.0 ohm or less?
- Yes, continue with Checking customer voltage with customer CB off (wired).
- No, inform the customer. Do not continue until the resistance is 1.0 ohm or less.